Radiamatic, Millivolts, Volts, Carbon, Oxygen Or Thermocouple Differential Inputs; Table 5-6 Set Up Wiring Procedure For Radiamatic, Millivolts, Volts, Carbon, Oxygen Or Thermocouple Differential Inputs (Except 0-10 Volts And -1 To 1 Volts); Figure 5-5 Wiring Connections For Radiamatic, Millivolts, Volts, Carbon, Oxygen Or Thermocouple Differential - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

5.4.4 Radiamatic, Millivolts, Volts, Carbon, Oxygen or Thermocouple Differential
Inputs
Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-6.
Table 5-6 Set Up Wiring Procedure for Radiamatic, Millivolts, Volts,
Carbon, Oxygen or Thermocouple Differential Inputs (Except 0-10 Volts and
Step
1
Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-5.
2
Place voltage source at zero before switching on.
Following calibration, turn off the voltage source prior to disconnecting it from the
3
instrument.
ATTENTION
For Radiamatic inputs only, set Emissivity value to 1.0.
See:
Subsection 3.12 – Configuration Set Up prompt INPUT 1, function prompt EMISSIV 1
Subsection 3.13 – Configuration Set Up prompt INPUT 2, function prompt EMISSIV 2
Subsection 3.14 – Configuration Set Up prompt INPUT 3, function prompt EMISSIV 3
Figure 5-5 Wiring Connections for Radiamatic, Millivolts, Volts, Carbon,
Oxygen or Thermocouple Differential Inputs (Except 0-10 Volts and –1 to 1
10/05
+
Millivolt or
Volt Source
_
UDC3500 Universal Digital Controller Product Manual
–1 to 1 Volts)
Action
28R
29+
30-
31R
32+
33-
34R
35+
36-
Volts)
Input Calibration
Input 3
Input 2
Input 1