Input 4 Set Up Group; Table 3-15 Input 4 Group Function Prompts - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

3.15 Input 4 Set Up Group

Introduction
This data deals with various parameters required to configure Input 4. Input 4 prompts
are not available unless Input 2 Type is set to 0-5V, 1-5V, 0-20mA or 4-20mA.
Function Prompts
Function Prompt
Lower Display
IN4 TYPE
ATTENTION
Changing the input
type will result in the
loss of Field
Calibration values and
will restore Factory
Calibration values.
Input 4 prompts will
not be available
unless Input 2 Type is
set to 0-5V, 1-5V, 0-
20mA or 4-20mA.
XMITTER4
IN4 HIGH
10/05

Table 3-15 INPUT 4 Group Function Prompts

Selections or
Range of Setting
Upper Display
DISABLE
0-20mA
4-20mA
0-5 V
1-5 V
B TC
R TC
E TC H
S TC
E TC L
T TC H
J TC H
T TC L
J TC M
W TC H
J TC L
W TC L
K TC H
100 PT
K TC M
100 LO
K TC L
200 PT
NNM H
500 PT
NNM L
RAD RH
NIC H
RAD RI
NIC L
LINEAR
PLAT H
SQROOT
PLAT L
–999. To 9999. Floating
(in engineering units)
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
INPUT 4 ACTUATION TYPE—This selection
determines what actuation you are going to use for
Input 4.
DISABLE—Disables Input
0-20mA—0 to 20 Milliamperes
4-20mA—4 to 20 Milliamperes
0-5 V—0 to 5 Volts
1-5 V—1 to 5 Volts
TRANSMITTER 4 CHARACTERIZATION—This
selection lets you instruct the controller to
characterize a linear input to represent a non-linear
one.
ATTENTION Parameter definitions are the same
as in IN1 TYPE.
INPUT 4 HIGH RANGE VALUE—This value in
engineering units is displayed for all inputs but can
only be changed for inputs configured for linear or
square root transmitter characterization.
See the example in IN1 HI.
Configuration
117