Output Algorithms; Table 10-17 Set-Up Group - Output Algorithms - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
10.7.8

Output Algorithms

Table 10-17 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Output Algorithms.
Parameter
Description
ID
Output
160
Algorithm
Relay Cycle
190
Time
Increments
Motor Time
75
for Positional
Proportional
Relay Output
243
Action
Current
153
Range for
Current
Duplex
Output
160
Algorithm
Loop2
Relay Output
175
Action Loop2
Current
153
Range for
Current
Duplex Loop2
362
Table 10-17 Set-up Group – Output Algorithms
Register
Address
Hex
Decimal
00A0
160
00BE
190
004B
075
00F3
243
0099
153
01A0
416
01AF
431
0199
409
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
INT
R/W
0 = Time Simplex
1 = Current Simplex
2 = Three Position Step or
Position Proportioning
3 = Time Duplex
4 = Current Duplex
5 = Current/Time Duplex
6 = Time/Current Duplex
INT
R/W
0 = 1 second increments
1 = 1/3 second increments
INT
R/W
5 to 1800 seconds
INT
R/W
0 = 1 OFF 2 OFF
1 = 1 ON 2 OFF
2 = 1 OFF 2 ON
3 = 1 ON 2 ON
INT
R/W
0 = Full (100%)
1 = Split (50%)
INT
R/W
0 = Time Simplex
1 = Current Simplex
2 = None
3 = Not Used
4 = Current Duplex
5 = Current/Time
6 = Time/Current
7 = Time Duplex
INT
R/W
0 = 1 OFF 2 OFF
1 = 1 ON 2 OFF
2 = 1 OFF 2 ON
3 = 1 ON 2 ON
INT
R/W
0 = 100%
1 = 50%
Data Range or
Enumerated Selection
10/05

Advertisement

Table of Contents
loading