Parameter
Description
ID
Alarm 2
228
Latching
Alarm 3
229
Latching
Alarm 4
230
Latching
Alarm 1 and 2
201
States (Read
Only)
Alarm 3 and 4
248
States (Read
Only)
Alarm Blocking
202
Diagnostic
154
Alarm
10/05
Modbus Read, Write and Override Parameters plus Exception Codes
Register
Data
Address
Type
Hex
Decimal
00E4
228
INT
00E5
229
INT
00E6
230
INT
00C9
201
INT
00F8
248
INT
00CA
202
INT
009A
154
INT
UDC3500 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = Non Latching
1 = Latching
R/W
0 = Non Latching
1 = Latching
R/W
0 = Non Latching
1 = Latching
R
State = 0 = Not in Alarm
State = 1 = In Alarm
Bit 0 = Alarm 1 SP1 State
Bit 1 = Alarm 1 SP2 State
Bit 2 = Alarm 2 SP1 State
Bit 3 = Alarm 2 SP2 State
Event = 0 = Low
Event = 1 = High
Bit 4 = Alarm 1 SP1 Event
Bit 5 = Alarm 1 SP2 Event
Bit 6 = Alarm 2 SP1 Event
Bit 7 = Alarm 2 SP2 Event
R
Event = 0 = Low
Event = 1 = High
Bit 0 = Alarm 3 SP1 Event
Bit 1 = Alarm 3 SP2 Event
Bit 2 = Alarm 4 SP1 Event
Bit 3 = Alarm 4 SP2 Event
State = 0 = Not in Alarm
State = 1 = In Alarm
Bit 4 = Alarm 3 SP1 State
Bit 5 = Alarm 3 SP2 State
Bit 6 = Alarm 4 SP1 State
Bit 7 = Alarm 4 SP2 State
R/W
0 = Disable
1 = Block Alarm 1
2 = Block Alarm 2
3 = Block Alarm 3
4 = Block Alarm 4
5 = Block Alarms 1 and 2
6 = Block Alarms 1,2,3
7 = Block Alarms 1,2,3,4
0 = Disable
R/W
1 = Alarm 1
2 = Alarm 2
3 = Alarm 3
4 = Alarm 4
5 = DISWARN