Configuration
Function Prompt
Lower Display
ALG1 INC
PCO SEL
PCT CO
PCT H2
ATM PRES
76
Selections or
Range of Setting
Upper Display
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
LP1OUT
LP2OUT
IN AL1
IN AL2
MANUAL
INPUT 3
0.020 to 0.350 (fractional
percent of CO)
1.0 to 99.0 (% H 2 )
590.0 to 760.0 (mm Hg)
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
ALGORITHM 1, INPUT C SELECTION—
Represents one of the following selections:
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
LOOP 1 OUTPUT—Should not be used for Three
Position Step Control applications
LOOP 2 OUTPUT—Should not be used for Three
Position Step Control applications
INPUT ALGORITHM 1
INPUT ALGORITHM 2
SOURCE OF PERCENT CARBON MONOXIDE—
Select either a fixed value for %CO value (PCT CO)
or use a live value from Analog Input 3.
MANUAL—Operator enters %CO as a Fixed Value
per the PCT CO configuration.
INPUT 3—Input 3 is used to provide the %CO value
to the Carbon Potential algorithm.
ATTENTION This prompt only appears when one
of the Carbon Potential algorithms is selected and
Input 3 is one of the following types: 0-20 mA, 4-20
mA, 0-5 V or 1-5 V.
PERCENT CARBON MONOXIDE—Used only when
a Carbon Potential algorithm is selected and PCO
SEL is set to MANUAL. Enter a value in percent of
carbon monoxide that is applicable for the enriching
gas used in fractional form.
FOR EXAMPLE:
Natural Gas = 20.0 % CO, then setting is 0.200
Propane Gas = 23.0 % CO, setting is 0.230
ATTENTION This prompt appears only when one
of the Carbon Potential algorithms is selected.
HYDROGEN CONTENT FOR DEWPOINT—Used
only when Dewpoint is selected. Enter a value for
the percentage of Hydrogen content that is
applicable.
ATMOSPHERIC PRESSURE COMPENSATION—
Used only when Relative Humidity is selected. Enter
the value of the atmospheric pressure of the
process.
10/05