Function Prompt
Lower Display
Y9 VALUE
Y10VALUE
Y11VALUE
Y12VALUE
Y13VALUE
Y14VALUE
Y15VALUE
Y16VALUE
Y17VALUE
TOTALIZE
ΣXXXXXXX
TOT SCAL
TOT SCR
10/05
Selections or
Range of Setting
Upper Display
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
0.00 to 99.99 %
DISABLE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
IN AL1
IN AL2
Σ*En
E0 = 1 x 10 0 = 1
E1 = 1 x 10 1 = 10
E2 = 1 x 10 2 = 100
E3 = 1 x 10 3 = 1,000
E4 = 1 x 10 4 = 10,000
E5 = 1 x 10 5 = 100,000
E6 = 1 x 10 6 = 1,000,000
UNLOCK
LOCK
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
Y9 INPUT VALUE (Y AXIS)
Y10 INPUT VALUE (Y AXIS)
Y11 INPUT VALUE (Y AXIS)
Y12 INPUT VALUE (Y AXIS)
Y13 INPUT VALUE (Y AXIS)
Y14 INPUT VALUE (Y AXIS)
Y15 INPUT VALUE (Y AXIS)
Y16 INPUT VALUE (Y AXIS)
Y17 INPUT VALUE (Y AXIS)
TOTALIZER FUNCTION calculates and displays the
total flow volume as measured by any analog input
or applied to either Input Algorithm 1 or Input
Algorithm 2 to totalize the compensated flow rate
being calculated by the algorithm. Displayed value is
eight digits with a configurable scale factor.
DISABLE—Disables the totalizer function.
INPUT 1—Input 1 is Totalized.
INPUT 2—Input 2 is Totalized.
INPUT 3—Input 3 is Totalized.
INPUT 3—Input 4 is Totalized.
INPUT 5—Input 5 is Totalized.
IN ALG1—Input Algorithm 1 is Totalized.
IN ALG2—Input Algorithm 2 is Totalized.
ATTENTION The totalizer should always be reset
to initialize the counters whenever it is enabled.
TOTALIZER VALUE—READ ONLY
Current Scale Factor (Upper Display)
Actual Current Totalized Value (Lower Display)
TOTALIZER SCALE FACTOR—Selects the desired
Scale Factor (i.e., Multiplier).
The desired factor is applied to the calculated value
to extend the maximum flow range that can be
displayed.
TOTALIZER RESET SECURITY LOCK—Allows the
totalizer to be reset.
UNLOCK—Allows the totalizer value to be reset.
LOCK—Prevents the totalizer value from being
reset.
Configuration
85