Monitoring and Operating the Controller
Step
Operation
17
Select Tuning
Set-up Group
18
Configure PIDSET
1 Values
Select Gain 2
19
Value
Configure Gain 2
20
Value
Select Rate 2 Min
21
Value
22
Configure Rate 2
Min Value
Select Options
23
Set-up Group
Select a Digital
24
Input
Select Auto-
25
Manual Station
Function
CAUTION
DO NOT SELECT
• In the CONTROL set up list, do not select SP TRACK as PV or RSP.
• In the SP RAMP set up list, do not select SP RATE as ENABLE.
• In the ALGORTHM set up list, do not select CONT ALG as PID B, ON-OFF, or
3PSTEP.
• In the Display menu when PIDSET # is displayed, DO NOT change the selection.
216
Press
Until you see:
Setup
Setup
Upper Display = SET
Lower Display = TUNING
Func
Configure the PIDSET 1 tuning parameters as needed by
Loop 1/2
the application.
and
or
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = GAIN2
Set the Gain 2 equal to:
or
Input 1 Span
Input 2 Span
If "PB" is selected under the Control Set Up group function
prompt "PBorGAIN", then set the PROP BD2 to
100 x
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = RATE2MIN
To configure:
or
0.00
Until you see:
Setup
Setup
Upper Display = SET
Lower Display = OPTIONS
Until you see:
Func
Upper Display = (available selections)
Loop 1/2
Lower Display = DIG IN1 or DIG IN2 or DIG IN3 or DIG IN4
This selection determines which Digital Input will be used
for Auto-Manual Station operation.
To select:
or
AM STA— Auto-Manual Station
UDC3500 Universal Digital Controller Product Manual