Input Calibration

5.4.8 Dual High Level Milliamperes Inputs

Refer to Figure 5-9 and wire the controller according to the procedure given in Table
5-11.

Table 5-11 Set Up Wiring Procedure for Dual High Level Milliampere Inputs

Step
1
Connect the copper leads from the calibrator to the input to be calibrated as shown in
Figure 5-9.
Place current source at zero before switching on.
2
Following calibration, turn off the current source prior to disconnecting it from the
3
instrument.
Milliampere
Source

Figure 5-9 Wiring Connections for Dual High Level Milliampere Inputs

270
250 ohms
250 ohms
250 ohms
250 ohms
+
_
250 ohms
Terminals for Input 1 are 35 (+) and 36 (-)
Terminals for Input 2 are 32 (+) and 33 (-)
Terminals for Input 3 are 29 (+) and 30 (-)
Terminals for Input 4 are 31 (+) and 33 (-)
Terminals for Input 5 are 28 (+) and 30 (-)