Honeywell UDC3500 Product Manual page 323

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Step
3
Determine if the
Communications board is faulty
by running a LOCAL
LOOPBACK TEST.
If the test fails, replace the
board. If the test passes, the
problem is most likely
elsewhere in the
communications network.
10/05
What to do
UDC3500 Universal Digital Controller Product Manual
How to do it
Disconnect the communications cable from the
rear terminals. Run the Local Loopback Test.
Setup
Setup
Press
key until you see:
Upper Display
SET UP
Lower Display
COM
Func
Loop 1/2
Press
key until you see:
Upper Display
DISABLE
Lower Display
LOOPBACK
Press
or
and you will see:
Upper Display
ENABLE
Lower Display
LOOPBACK
Lower
Lower
Lower
Display
Display
Display
Press
key and you will see:
Upper Display
START
Lower Display
LOOPBACK
Then you will see either PASS or FAIL in the
Upper Display. The test will run until the
operator disables it or until the unit is power-
cycled.
If you see FAIL, go to Step 4. If you see PASS,
then the problem is most likely not in the
instrument, but somewhere else in the
network. Reconnect the communications cable
and then go to Step 7.
Troubleshooting/Service
309