Function Prompt
Lower Display
HIGH VAL
10/05
Selections or
Range of Setting
Upper Display
High Scale Value within
the range of the selected
variable to represent the
maximum output (20 mA)
UDC3500 Universal Digital Controller Product Manual
Parameter
Definition
CURRENT OUTPUT HIGH SCALING FACTOR—
Used only when CUR OUT is any selection other
than DISABLE. This is a value in engineering units
used to represent all CUR OUT parameters except
Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
Configuration
105