Table 2-7 Dual Loop Controller - Loop 2 Output Functionality And Restrictions - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Installation
Not Needed = The Second Current Output is Not Needed for this output form and does not have to be
installed. If it is installed, then it can be used to perform an Auxiliary Output function.
Loop 2 Output
Output #2
Algorithm
Option
Selection
Time Simplex or
Third Current
ON-OFF Simplex
All Other
Time Duplex or
Third Current
ON-OFF Duplex
All Other
Current Simplex
Third Current
All Other
Current Duplex
Third Current
100 %
Second or Third
All Other
Current Out =
COOL and HEAT
Current Duplex
Third Current
50 % ***
Second Current =
All Other
HEAT
Third Current =
COOL
Current/Time
Third Current
Second or Third
Current = COOL
All Other
Time = HEAT
Time/Current
Third Current
Time = COOL
Second or Third
All Other
Current = HEAT
NUL2 =
Not Used on Loop 2 – This particular output is not used for the selected Second Loop
Output type, but it may be used for the First Loop Output type. Refer to the selection made
in Table 2-6.
N/A2 =
Current Duplex 50% is Not Available on Loop 2 unless the Third Current Output is
installed.
Not Needed = The Second Current Output is Not Needed for this Loop 2 Output. If it is installed, and it is
not used for Loop 1 Output, then it can be used to perform an Auxiliary Output function.
Refer to the selection made in Table 2-6.
* The Second Current Output and Ethernet Communications are mutually exclusive.
26
Table 2-7 Dual Loop Controller – Loop 2 Output Functionality and
Function of
Output #2
NUL2
Output
NUL2
Options
NUL2
Output
NUL2
Options
Loop 2 HEAT
Output
NUL2
Options
Loop 2 HEAT
Output
and COOL
NUL2
Options
Loop 2 HEAT
Output
N/A2
Options
Loop 2 COOL
Output
NUL2
Options
Loop 2 HEAT
Output
NUL2
Options
UDC3500 Universal Digital Controller Product Manual
Restrictions
1st Current
2nd Current
Output
Output *
NUL2
Not Needed
NUL2
Not Needed
NUL2
Not Needed
NUL2
Not Needed
NUL2
Not Needed
NUL2
Loop 2
HEAT
NUL2
Not Needed
NUL2
Loop 2
HEAT and
COOL
NUL2
Loop 2
COOL
N/A2
N/A2
NUL2
Not Needed
NUL2
Loop 2
COOL
NUL2
Not Needed
NUL2
Loop 2
HEAT
Relay #3
Relay #4
Loop 2
Alarm 2
HEAT
Loop 2
Alarm 2
HEAT
Loop 2
Loop 2
HEAT
COOL
Loop 2
Loop 2
HEAT
COOL
Alarm 3
Alarm 2
Alarm 3
Alarm 2
Alarm 3
Alarm 2
Alarm 3
Alarm 2
Alarm 3
Alarm 2
N/A2
N/A2
Loop 2
Alarm 2
HEAT
Loop 2
Alarm 2
HEAT
Loop 2
Alarm 2
COOL
Loop 2
Alarm 2
COOL
Relay #5
Alarm 1
Alarm 1
Alarm 1
Alarm 1
Alarm 1
Alarm 1
Alarm 1
Alarm 1
Alarm 1
N/A2
Alarm 1
Alarm 1
Alarm 1
Alarm 1
10/05

Advertisement

Table of Contents
loading

Table of Contents