4-10 Connecting Event Output (relay output)

Event outputs EV1 and EV2 are 1a contact, and event output EV3 is 1a1b. Event outputs are connected on the
standard terminal base.
Handling Precautions
4-12
Standard terminal base
4
Load
5
Power supply
6
Load
7
Power supply
8
Load
9
Power supply
10
When switching small currents, connect a bleeder resistor to allow current flow of
the minimum relay switching input (10mA min.).
Contact rating, resistive load
EV1 1a
1A (30/250Vdc)
Contact rating, resistive load
EV2 1a
1A (30/250Vdc)
Contact rating, resistive load
EV3 1a1b
2A (30/250Vdc)
Minimum switching current: 10mA