Control Loop 2; Table 10-24 Set-Up Group - Control2 - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

10.7.15

Control Loop 2

Table 10-24 lists all the register addresses and ranges or selections for the function
prompts in Set-up Group Control2.
Parameter
Description
PV Source Loop2
Link Modes and Set
Point
Tuning Parameter
Selection Loop2
Automatic Loop2
Switchover Value
PID1 to PID2 (used
with ID 172 )
Automatic Loop2
Switchover Value
PID2 to PID3 (used
with ID 172 )
Automatic Loop2
Switchover Value
PID3 to PID4 (used
with ID 172 )
10/05
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-24 Set-up Group – Control2
Register
Address
ID
Hex
Decimal
133
0185
389
132
0184
388
172
01AC
428
9
0109
265
10
010A
266
11
010B
267
UDC3500 Universal Digital Controller Product Manual
Data
Access
Type
Enumerated Selection
INT
R/W
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input Algorithm 1
6 = Input Algorithm 2
7 = None
0 = Disable
INT
R/W
1 = AutoMan
2 = SP1
3 = AM + SP1
INT
R/W
0 = One set only
1 = 2 sets keyboard
2 = 2 sets with PV
3 = 2 sets with setpoint
(SP) automatic
switchover
4 = Four sets Keyboard
5 = Four sets Auto Switch
PV
6 = Four sets Auto Switch
SP
FP
R/W
Within the PV Range in
engineering units
FP
R/W
Within the PV Range in
engineering units
FP
R/W
Within the PV Range in
engineering units
Data Range or
selected
automatic switchover