Input 1 Parameters Set Up Group; Table 3-5 Input 1 Group Function Prompts - Honeywell UDC3300 Product Manual

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

3.8

Input 1 Parameters Set Up Group

Introduction
Function prompts
Table 3-5
Input 1 Group Function Prompts
Function Prompt
Lower Display
DECIMAL
UNITS
IN1 TYPE
XMITTER
(not available for FM
models)
IN1 HI
IN1 LO
1/01
This data deals with various parameters required to configure Input 1.
Table 3-5 lists all the function prompts in the "INPUT 1" Set Up group.
Function
Name
Decimal Point Location
XXXX
XXX.X
XX.XX
Temperature Units
DEG F
DEG C
NONE
Input 1 Actuation Type
B TC
E TC H
E TC L
J TC H
J TC L
K TC H
K TC L
NNM H
NNM L
NM90 H
NM90 L
NIC TC
R TC
S TC
T TC H
*not available for FM models
Transmitter
B TC
Characterization
E TC H
E TC L
J TC H
J TC L
K TC H
K TC L
NNM H
NNM L
NM90 H
NM90 L
NIC TC
R TC
Input 1 High Range
–999. to 9999.
Value (Linear Inputs and
in engineering units
Radiamatic RI only)
Input 1 Low Range
–999. to 9999.
Value (Linear Inputs and
in engineering units
Radiamatic RI only)
UDC3300 Limit Controller Product Manual
Selections or
Range of Setting
Upper Display
None
One
Two
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
0-20mA*
4-20mA*
0-10mV*
0-50mV*
0-5 V*
1-5 V*
0-10V*
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
LINEAR
SQROOT
Continued on next page
Factory Setting
XXXX
NONE
0-10mV
(K TC H for FM only)
LINEAR
1000
(2400 for FM only)
0
27

Advertisement

Table of Contents
loading

Table of Contents