Removal Of The Heat Exchanger - Daikin E Series Service Manual

Inverter pair wall mounted type e-series
Hide thumbs Also See for E Series:
Table of Contents

Advertisement

SiBE04-624

1.12 Removal of the Heat Exchanger

Procedure
Step
1. Remove the refrigerant
piping
Put a wooden block
1
under the indoor unit
and pull out the
refrigerant piping, drain
hose, connection
wirings, and so on.
Disconnect the flare
2
nut of the connection of
gas pipe with 2
spanners.
Disconnect the flare
3
nut of the connection of
liquid pipe with 2
spanners.
Caution
From the point of
view of
environmental
protection, be sure to
use a vacuum pump
for air purging.
Removal Procedure
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Indoor Unit
Points
Preparation
Remove the drain hose
according to "Removal of
Drain Hose".
Caution
In pump-down work, be sure
to stop the compressor
before disconnecting the
refrigerant pipe. If the
refrigerant pipe is
disconnected with the
compressor running and the
stop valve being open, air
may be sucked in and cause
an over-pressure in
refrigeration cycle, thus
resulting in pipe rupture or
accidental injury.
Be careful that remaining
drain will not wet the floor.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
Carry out the removal works
with 2 pair of spanners.