Others; Test Run From The Remote Controller - Daikin E Series Service Manual

Inverter pair wall mounted type e-series
Hide thumbs Also See for E Series:
Table of Contents

Advertisement

Others

1. Others
1.1
Test Run
For Heat pump
In cooling mode, select the lowest programmable temperature; in heating mode, select the
highest programmable temperature.
Trial Operation and Testing
1. Measure the supply voltage and make sure that it falls in the specified range.
2. Trial operation should be carried out in either cooling or heating mode.
3. To perform a test run for humidifying operation, activate test run mode from the remote
4. Operate the unit in accordance with the operation manual to check that it operates normally.
Trial operation from Remote Controller
(1) Hold the "CLOCK" button for 5 seconds.
(2) Display "
(3) "T" will be displayed and the unit will enter test run mode.
(4) Press the button corresponding to the test run mode.
298
from the Remote Controller
Trial operation may be disabled in either mode depending on the room temperature.
After trial operation is complete, set the temperature to a normal level.
(26°C to 28°C in cooling mode, 20°C to 24°C in heating mode)
For protection, the system disables restart operation for 3 minutes after it is turned off.
controller following the instructions below and press the "HUMIDIFY" button.
Even when the air conditioner is not operating, it consumes some electric power. If the
customer is not going to use the unit soon after it is installed, turn off the breaker to avoid
wasting electricity.
(The matrix display will appear on the remote controller.)
" on the matrix display of the remote controller and press the "CLOCK"
button.
Test run mode will stop automatically after around 30 minutes.
Press the ON/OFF button to force the test-run to stop.
(2)
(3)
(1), (2)
Cooling
(4) Test run mode
(R5906)
SiBE04-624
Stop
Humidifying
Heating
(R5988)
Others