Draft Prevention (Hot Start) - Daikin E Series Service Manual

Inverter pair wall mounted type e-series
Hide thumbs Also See for E Series:
Table of Contents

Advertisement

SiBE04-624

2.29 Draft Prevention (HOT Start)

Outline
Draft prevention control is done to prevent a cold draft feeling when the unit is started up in
heating operation. This will happen if the indoor coil temperature drops.
Detail
The outdoor unit will prevent a cold draft by monitoring the indoor heat-exchanger thermistor. It
will increase the minimum compressor frequency if the indoor heat exchanger drops below
33°C. If the coil is not hot enough, the indoor fan will not be started at the set speed.
The fan speed will be released step by step. The limitation of the fan speed will be lifted when
the indoor heat exchanger temperature rises above F°C.
28 class
42 class
50 class
Function and Control
F min = - 2Hz/120sec
35˚C
No change (steady area)
33˚C
F min = + 4Hz/120sec
Fan speed
M
ML
Upper
L
limitation
LL
LLL
A
A
B
10
25
10
25
10
25
No limitation
B
C
D
E
F
Temperature
C
D
33
34
35
37
35
37
Main Functions
(R5912)
(˚C)
(R5911)
E
F
35
36
38
39
38
39
61