SiBE04-624
Troubleshooting
*Output overcurrent may caused by improper wiring inside the machine. If the
Check No.3
Refer to P.203
Check No.15
Refer to P.207
Check No.16
Refer to P.208
Check No.14
Refer to P.206
Service Diagnosis
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
machine stops due to output overcurrent after connecting or disconnecting wires
to replace part, check wiring for proper connection.
Is the stop valve
fully opened?
YES
Check that the fault condition
appears whenever turning on the
power supply again after turning
it off.
Repeated?
YES
Turn off the power supply, and
disconnect U, V, and W
harnesses
Check No.14
Check the inverter by the
inverter checker*
Is there any LED
turned off?
NO
Check No.15
Check the power transistor
Is it OK?
YES
Turn off the power supply, replace
the harnesses, and restart the
compressor after turning on the
power supply again.
Check the supply voltage
Rated voltage?
YES
Short-circuit or
breakage between compressor's
coil phases?
NO
Check No.16
Discharge pressure check
Check No.3
Installation condition check
NO
Monitor the supply voltage,
discharge and suction
pressures, and other factors for
a long term.
NO
Possible causes
· Momentary supply voltage drop
· Compressor motor overloaded
· Short circuit
YES
NO
NO
YES
Troubleshooting
Open the stop valve fully.
Keep on using as it is.
}
(monitoring)
Check connectors and
other fittings of electric
components .
*Inverter checker
Part No.: 1225477
Rectify the power supply or
replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Rectify the power supply.
Replace the compressor.
(R6016)
187