Dc Fan Lock - Daikin E Series Service Manual

Inverter pair wall mounted type e-series
Hide thumbs Also See for E Series:
Table of Contents

Advertisement

SiBE04-624

2.20 DC Fan Lock

E7
Remote
Controller Display
Outdoor Unit LED
A5
Display
Method of
Identify the fan motor system fault based on fan speed detected by Hall IC during high pressure
fan motor running.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.23
Refer to P.211
Service Diagnosis
5 5 ( - )
When the fan motor is running, the fan does not rotate for 60 sec. or more.
Shut down when the error repeats 16 times
Clear condition: The fan continuously rotates for 11 min.(without fault)
Failure in fan motor
Disconnection or improper connection of harness/connector between fan motor and PCB
The fan does not rotate because it gets caught in foreign matter
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the
connector of the fan motor
disconnected?
NO
Is there any
foreign matter around
the fan?
NO
Try to operate
Check No. 23
Check the outdoor unit PCB for
rpm command pulse input
Is the pulse input?
YES
YES
YES
NO
Troubleshooting
Turn off the power supply,
then insert the connector.
Remove them.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB.
(R6011)
167