SiBE041101
1.7

Removal of Indoor Heat Exchanger

Procedure
Step
1. Disconnect the refrigerant
piping.
Remove the screws
1
which fix the indoor
heat exchanger to the
installation plate.
2
Lift the indoor unit with
a wooden base.
Lift up the indoor unit
3
slightly and pull out the
drain hose. (The
illustration is for the
case of left piping.)
4
Disconnect the piping
connection with 2
wrenches.
Caution
From the viewpoint of
global environment
protection, be sure to
use a vacuum pump
for air purging.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Drain hose
Points
(R8103)
Caution
In pump-down work, be sure
to stop the compressor
before disconnecting the
refrigerant pipe. If the
refrigerant pipe is
disconnected with the
compressor operating and
the stop valve open, air may
be sucked in to generate an
(R8104)
over-pressure in refrigeration
cycle, thus resulting in pipe
rupture or accidental injury.
Place a plastic sheet under
the drain pan to prevent
from wetting the floor with
remaining drain.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
(R8101)
Carry out the removal works
with 2 wrenches.
When the pipings are
disconnected, protect the
both openings of pipe side
and unit side from entering
of moisture.
(R8105)
Indoor Unit
152