How To Replace The Drain Plug And Drain Hose; To Set The Different Addresses - Daikin E Series Service Manual

Inverter pair wall mounted type e-series
Hide thumbs Also See for E Series:
Table of Contents

Advertisement

SiBE04-624
6.

How to replace the drain plug and drain hose.

• Replacing onto the left side
1) Remove the insulation fixing screws on the right to
remove the drain hose.
2) Reattach the insulation fixing screw on the right as it
was.
*(Forgetting to attach this may cause water
leakages.)
3) Remove the drain plug on the left side and attach it
to the right side.
4) Insert the drain hose and tighten with included
indoor unit fixing screw.
F
7.
How to set the different addresses.
• When 2 indoor units are installed in one room, the
2 wireless remote controllers can be set for different
addresses.
1) Remove the front grille. (3 screws)
2) Cut the address jumper "JA". (See Fig. 1)
3) Remove the remote controller lid and cut the
address jumper "J4". (See Fig. 2)
System Configuration
Drain hose attachment position
* The drain hose is on the back of the unit.
Left side
Front side of unit
Attachment on the left side
Indoor unit
F
fixing screw
Drain hose
How to set drain plug.
Do not apply lubricating oil (refrigerant
oil) when inserting.
Application of causes deterioration and
drain leakage of the plug.
Insert a hexagon wrench (4mm).
Fig. 1
Cut JA.
Fig. 2
Cut section
Installation Manual
Right side
Attachment on the right side (factory default)
Insulation
fixing screw
Drain hose
Electric parts box cover