To fill the domestic hot water tank ....... 42 6 Preparation 7.8.6 To insulate the water piping ......... 42 Overview: Preparation............... 21 Connecting the electrical wiring..........42 Preparing the installation site ............ 22 Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
About cleaning the water filter in case of trouble....... 85 11.5.1 To remove the water filter ........... 85 11.5.2 To clean the water filter in case of trouble ....85 ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Make sure installation, testing and applied materials comply with applicable legislation (on top of the ▪ In potentially explosive atmospheres. instructions described in the Daikin documentation). ▪ In places where there is machinery that emits electromagnetic waves. Electromagnetic waves may disturb the control system, CAUTION and cause malfunction of the equipment.
▪ Only use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system. ▪ Charge the liquid refrigerant as follows: ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Format: Paper (in the box of the indoor unit) ▪ Outdoor unit installation manual: ▪ Installation instructions ▪ Format: Paper (in the box of the outdoor unit) Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). 3.2.1 To unpack the outdoor unit ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). Installer reference guide at a glance...
This chapter contains information about: Bolts, nuts, washers, spring washers and wire clamp ▪ Identifying the outdoor unit ▪ Identifying the indoor unit ▪ Combining the outdoor unit with options Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1). For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
For installation instructions, see the installation manual of the LAN design leaving water temperature? adapter. Once the space heating/cooling requirements are clear, we recommend to follow the setup guidelines below. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Code: [C-07] user interface. Benefits 0 (Single zone): Main Number of water temperature ▪ Wireless. The Daikin external room thermostat is available in a zones: wireless version. ▪ #: [4.4] ▪ Efficiency. Although the external room thermostat only sends ON/ OFF signals, it is specifically designed for the heat pump system.
Example: If the heat pump system is used to heat up one floor underfloor heating is shut off by the shut-off valve. where all the rooms have the same heat emitters. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 13
▪ Easy. Same installation as for one room, but with thermostatic valves. Heat pump convectors – Multiple rooms Setup Main leaving water temperature zone ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ For each room with heat pump convectors: The desired room temperature is set via the remote controller of the heat pump convectors. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Bivalent operation is only possible for space heating, NOT for domestic hot water production. Domestic hot water is always produced by the DHW tank connected to the indoor unit. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 16
Automatic system complies with applicable legislation. Boiler Boiler ▪ Daikin is NOT responsible for incorrect or unsafe NOTICE situations in the auxiliary boiler system. ▪ Make sure the auxiliary contact has enough differential ▪ Make sure the return water to the heat pump does NOT exceed or time delay to prevent frequent changeover between 55°C.
▪ 3 showers you can use the following energy sources: ▪ 1 bath ▪ Thermodynamic cycle of the heat pump ▪ 3 sink volumes ▪ Electrical booster heater ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ If applicable legislation requires disinfection of the water piping until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Power meter 2: Measures the rest (i.e. indoor unit, backup heater and optional booster heater). Setup ▪ Connect power meter 1 to X5M/5 and X5M/6. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Power limitation activated by digital inputs Power limitation is also useful in combination with an energy management system. The power or current of the entire Daikin system is limited Outdoor unit dynamically by digital inputs (maximum four steps). Each power Indoor unit...
Full outdoor unit operation ▪ Preparing the installation site Booster heater turned ON Backup heater step 1 turned ON ▪ Preparing the refrigerant piping Backup heater step 2 turned ON ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Do NOT hang the unit on a ceiling. Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short circuit (suction of discharge air). This may result in: Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Suction grille ▪ Mind the following spacing installation guidelines: Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 24
▪ Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes. WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. NOTICE ▪...
Page 25
▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold). ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
"Installation" chapter, respecting the water inlet and outlet. ▪ Connecting piping – Force. Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Domestic hot water tank – Capacity. To avoid stagnation of water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Schrader each metre below 7 m. valve of the expansion vessel. ▪ Check water volume does exceed the maximum allowed water volume. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
At that moment, the outdoor unit compressor will not operate. The wiring to the unit is different depending on whether the power supply is interrupted or not. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Optional equipment 3‑way valve 100 mA Power supply for 4+GND booster heater and thermal protection (from indoor unit) Power supply for 2+GND 13 A booster heater (to indoor unit) Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
4 If you have to do work behind the user interface panel or upload Switch box cover new software into the user interface, open the user interface Switch box panel. User interface panel Open 1 Remove the front panel. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Protecting the unit against snow and wind by installing a snow cover and baffle plates. See "Preparing installation site" in "6 Preparation" [ 4 21]. (mm) Maximum snowfall height Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ (1) Put the unit into position (using the sling to the left and the handle to the right). ▪ (2) Remove the sling (by pulling 1 side of the sling). ▪ (3) Fix the unit. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
In short, the drain pan must be installed level (with a tolerance of 1° at all sides) and as follows: Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Tilt the top of the unit against the wall at the position of the wall bracket. ▪ Slide the bracket on the back of the unit over the wall bracket. Make sure the unit is fixed properly. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Use caution when passing copper tubes through walls (see figure below). Drain pan connector It is recommended to use a tundish to collect the water. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Always protect the surrounding surfaces (e.g. insulation foam) 2 Remove burrs with the cut surface facing down so that the from heat when brazing. chips do NOT enter the pipe. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Result: The valve is now open/closed. To handle the stem cap ▪ The stem cap is sealed where indicated with the arrow. Do NOT damage it. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
−0.1 MPa (−1 bar). same pump for other refrigerants may damage the pump 4 After turning the pump OFF, check the pressure for at least and the unit. 1 hour. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
If pump down is needed in case of dismantling or relocating the consists of the following stages: down" [ 4 91] for more details. system, see "13.2 To pump 1 Determining how much refrigerant to charge. 2 Charging refrigerant. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
7.8.3 To connect the water piping NOTICE Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ The refrigerant piping is connected and checked Stranded conductor wire Round crimp-style terminal ▪ The water piping is connected ▪ Use the following methods for installing wires: Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
4 Reattach the switch box cover. 5 Optional: Attach the wire clamp (accessory) to the screw of the refrigerant piping cover, and fix the cables to it with a cable tie. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
▪ Normal kWh rate power supply Interconnection cable (=main power supply) supply Normal kWh rate power supply ▪ Preferential kWh rate power supply Preferential power supply contact Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
21 29 2 Fix the cable with cable ties to the cable tie mountings. YC Y1 YC Y1 Y2 Y3 Y4 Installation of EKRP1HBAA is required. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
OR a safety thermostat. Installation of EKRP1HBAA is required. 2 Fix the cable with cable ties to the cable tie mountings. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
To restart the 1234 Installer settings configuration wizard, > Configuration wizard. To access Installer settings, see commands" [ 4 48]. "8.1.1 To access the most used Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
This way the unit will be able to run properly. Afterwards, more detailed settings can be done via the menu structure if required. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Leaving water temperature setpoint c3: Screen with weather-dependent curve c4: Screen with schedule g3 Room thermostat type: ▪ : Daikin user interface used as room 8.3.2 Home screen thermostat Press the button to go back to the home screen. You see an ▪...
Turn heating/cooling functionality and Operation increase/decrease. domestic hot water preparation on or off. Submenu Turn or press the left dial to go to the submenu. 8.3.4 Menu screen Example: ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
3 Go to [1.2]: Room > Heating schedule. Confirm changes and proceed. To clear the content of the week schedule: 1 Select the name of the current schedule. User defined 1 Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 53
4 Confirm the changes. first day you programmed. Thus, the last 5 Select Saturday. programmed action is valid up to the first action of next Monday. 6 Select Copy. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
[1] Room. temperature drops below 4°C the room again, and the leaving water temperature setpoint will screen" [ 4 51]. "8.3.5 Setpoint be lowered. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
NOT guaranteed. ▪ In Weather dependent LWT setpoint mode, the scheduled actions consist of desired shift actions, either preset or custom. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 56
Heating WD curve Cooling WD curve Set weather-dependent heating for the main zone (if [2.4]=1 or 2): Set weather-dependent cooling for the main zone (if [2.4]=2): Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 57
▪ 1: Fancoil unit ▪ 2: Radiator The setting Emitter type influences the space heating setpoint range and the target delta T in heating as follows: ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 58
35°C. In such case, the unit will realize a temperature difference of ▪ 5°C~18°C 5°C, which means that the entering water temperature is around Cooling maximum: [2.8.4] [9-03] 30°C. ▪ 18°C~22°C Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 59
This results in: ▪ stable room temperatures, exactly matching desired temperature (higher comfort level) ▪ less on/off cycles (lower noise level, higher comfort and higher efficiency) ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
[3.4] Setpoint mode ▪ Fixed ▪ WD heating, fixed cooling ▪ Weather dependent Heating WD curve Set weather-dependent heating for the additional zone (if [3.4]=1 or Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 61
(= the leaving water temperature zone with the highest leaving water temperature in heating operation and the lowest leaving water temperature in cooling operation) ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
(e.g. when in heating, this value is related to the desired heating end user indicates which operation is allowed for each month. temperature). Example: A unit is configured as following: Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 63
When the space heating/cooling operation is OFF, the pump is always OFF. When space heating/cooling operation is ON, you have the choice between these operation modes: a Main LWT zone ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 64
Space heating/cooling control b (l/min) b (l/min) b Off c On d Heating demand (by external room thermostat or room thermostat) e Pump operation Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
The storage economic temperature denotes the lower desired This function is ONLY applicable in heating mode. tank temperature. It is the desired temperature when a storage economic action is scheduled (preferably during day). ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 66
NOT be [5.7.1] [2‑01] Activation successful and the applicable warning AH will be generated. ▪ 0: No ▪ 1: Yes Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 67
Applicable when domestic hot water preparation is scheduled Range: 0°C~10°C +reheat. When the tank temperature drops below the reheat temperature minus the reheat hysteresis temperature, the tank heats up to the reheat temperature. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Set the local time and date NOT use the most quiet level. To check if quiet mode is active is displayed on the home screen, quiet mode is active. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 69
To set the electricity price Gas price=8.58 1 Go to [7.5.1]/[7.5.2]/[7.5.3]: User settings > Calculation of the electricity price: Electricity price > High/Medium/Low. Electricity price=Actual electricity price+Incentive/kWh ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Domestic hot water OUT Recirculation connection DHW pump schedule Program a schedule for the DHW pump (only for field supplied domestic hot water pump for secondary return). Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 71
During normal operation, the capacity of the second step of Example: Only allow the booster heater to operate during the night. the backup heater at nominal voltage is equal to [6‑03]+[6‑04]. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 72
We recommend to set Emergency to Automatic if the house is unattended for longer periods. Code Description [9.5] ▪ 0: Manual ▪ 1: Automatic Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 73
[8-01]+ [8-01]+ [8-04] [8-04] Range: 0°C~20°C [8-02] [8-02] [8-01] [8-01] [5-03] [4-02] [F-01] 35°C Ambient (outdoor) temperature Time Anti-recycle timer Maximum running time domestic hot water ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 74
X2M/5‑6) and the backup heater is NOT [9.9.A] [5-0A] Limit 2: 0 kW~20 kW connected to the preferential kWh rate [9.9.B] [5-0B] Limit 3: 0 kW~20 kW power supply. [9.9.C] [5-0C] Limit 4: 0 kW~20 kW Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 75
▪ 2 1/kWh: Installed provide the space heating, either the indoor unit or an auxiliary ▪ 3 10/kWh: Installed boiler. ▪ 4 100/kWh: Installed ▪ 5 1000/kWh: Installed ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 76
Auxiliary boiler active Set all electricity prices ([7.5.1]~[7.5.3]) to "0" in the menu structure. Auxiliary boiler inactive Also set the following values: NOTICE Do NOT use overview settings! Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 77
INFORMATION guideline 5 when bivalent operation function is enabled. Protective functions – "Installer-on-site mode". The Daikin shall NOT be held liable for any damage resulting software is equipped with protective functions, such as from failure to observe this rule. room antifrost. The unit automatically runs these functions when necessary.
About Connection status User profile Operation Room Space heating/cooling Tank Setpoint screen INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
The indoor unit is properly mounted. To perform an air purge. The outdoor unit is properly mounted. To perform a test run. To perform an actuator test run. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Conditions: Make sure all operation is disabled. Go to [C]: operation, the unit may NOT operate or may NOT deliver Operation and turn off Room, Space heating/cooling and Tank the required capacity. operation. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
In this case, the backup heater will perform the screed dryout and supply the leaving water without heat pump operation. Desired leaving water temperature (15~55°C) Duration (1~72 h) Action step 1 Action step 2 Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Stop UFH screed dryout ▪ The yearly maintenance of the indoor unit To manually stop underfloor heating screed dryout: 1 Go to [A.4.3]: Commissioning > UFH screed — dryout ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
To make sure this water originates from the tank, check after a tank sink...). heat up cycle. 4 Open the drain valve for a couple of seconds (c). Result: Water and dirt will come out. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Collect the drained water in a bottle, sink, … using the installed drain hose. 7 Remove the 2 clips that fix the water filter. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
For any other problem, contact your installer. You can find the contact/helpdesk number via the user interface. 12.1 Overview: Troubleshooting This chapter describes what you have to do in case of problems. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
"6.5 Preparing electrical wiring" [ 4 29] and "7.9.8 To Possible causes Corrective action connect the main power The expansion vessel is broken Replace the expansion vessel. supply" [ 4 44]. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
4 hours NO domestic hot water tapping is expected. ▪ The water pressure ▪ Whether there is air in the system ▪ The air purge operation Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Detailed error Description OU: High pressure peak code cut / freeze protection Water flow problem problem Water flow problem during OU: PCB defect domestic hot water production ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
User interface communication problem INFORMATION Connection with LAN adapter For more details, see the service manual. lost Connection with room thermostat lost No connection with room thermostat Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Gas stop valve 13.3 To start and stop forced cooling 1 Turn OFF the power. 2 Remove the switch box cover. 2× 3 Remove the service PCB cover. ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
14 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 14.1 Piping diagram: Outdoor unit 7.0 CuT...
* Ambient sensor user interface Legend R2T (A1P) Outlet backup heater thermistor Main PCB R2T (A2P) * External sensor (floor or ambient) * On/OFF thermostat (PC=power circuit) ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 96
Only for wired On/OFF Only for wired On/OFF (5) Ext. thermistor (5) External thermistor thermostat thermostat Switch box Only for wireless On/OFF Only for wireless On/OFF thermostat thermostat Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Page 97
Power limitation A8P: X801M: 4-5 2x0.75 X5M: 11-12 demand input 4 signal A14P: P1-P2 user interface communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D111879D ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
(i.e. if the piping length is <27 m) are NOT subjected to any requirements to the installation room. ▪ Charges >1.9 kg are NOT allowed in the unit. Installer reference guide ERGA04~08DAV3(A) + EHBH/X04+08DA Daikin Altherma 3 R W 4P496758-1B – 2019.10...
If dm=1.55 kg, consider the value that corresponds to "dm=1.6 kg". ERGA04~08DAV3(A) + EHBH/X04+08DA Installer reference guide Daikin Altherma 3 R W 4P496758-1B – 2019.10...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with product according instructions accompanying documentation.
Page 102
2/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: Disabled 1: Enabled 1.4.2 [2-05] Room setpoint 4~16°C, step: 1°C 12°C └─...
Page 103
3/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value Additional zone [2-0D] Emitter type 0: Underfloor heating 1: Fancoil unit 2: Radiator └─ Setpoint range 3.8.1 [9-05] Heating minimum 15~37°C, step: 1°C 25°C...
Page 104
4/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [0-0B] Leaving water value for high ambient temp. for DHW WD curve. 35~[6-0E]°C, step: 1°C 55°C [0-0C] Leaving water value for low ambient temp. for DHW WD curve. 45~[6-0E]°C, step: 1°C 60°C [0-0D]...
Page 105
5/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [0-04] Leaving water value for high ambient temp. for LWT add zone cooling WD curve. [9-07]~[9-08]°C, step: 1°C 8°C [0-05] Leaving water value for low ambient temp.
Page 106
6/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.9.2 [4-09] Type 0: Current 1: Power 9.9.3 [5-05] Limit 0~50 A, step: 1 A 50 A 9.9.4 [5-05] Limit 1 0~50 A, step: 1 A...
Page 107
7/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [1-04] Weather dependent cooling of the main leaving water temperature zone. 0: Disabled 1: Enabled [1-05] Weather dependent cooling of the additional leaving water temperature zone 0: Disabled 1: Enabled [1-06]...
Page 108
8/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [4-0A] Backup heater configuration 0: 1 (*1) 1: 1/1+2 (*2) (*3) 2: 1/2 3: 1/2 + 1/1+2 in emergency [4-0B] Automatic cooling/heating changeover hysteresis.
Page 109
9/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [8-08] What is the desired eco main LWT in cooling? [9-03]~[9-02], step: 1°C 20°C [8-09] [9-01]~[9-00], step: 1°C What is the desired comfort main LWT in heating? 35°C [8-0A]...
Page 110
10/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [E-00] Which type of unit is installed? 0: LT split [E-01] Which type of compressor is installed? [E-02] What is the indoor unit software type? R/W (*6) 0: Reversible (*6)