Removal Of Indoor Heat Exchanger - Daikin FTK15JEVM Service Manual

Removal procedure 1.5/2.0/2.5/3.2/3.5/4.6 kw class 9000/12000 btu/h class
Table of Contents

Advertisement

Si041051

8. Removal of Indoor Heat Exchanger

Procedure
Step
1. Disconnect the refrigerant
piping.
1
Remove the screws
which fix the indoor unit
to the installation plate.
2
Lift the indoor unit with
a wooden base.
Pull out the drain hose.
3
Disconnect the flare nut
4
for gas piping.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Wooden base
Extension drain hose
Connecting wires
Removal of Indoor Heat Exchanger
Preparation
Be sure to stop the
compressor before
disconnecting the refrigerant
pipe. If the refrigerant pipe is
disconnected with the
(R17298)
compressor running and the
stop valve opened, air may be
sucked in to generate an
over-pressure in the
refrigeration cycle, thus
resulting in pipe rupture or
accidental injury.
(R17299)
Drain hose
(R17300)
From the viewpoint of global
environmental protection,
make sure to use a vacuum
pump for air purging.
(R17301)
Points
Remove the electrical box
according to the "Removal
of Electrical Box / Vertical
Blades".
Caution
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
Place a plastic sheet under
the drain hose as remaining
drain may leak.
Carry out the removal work
with 2 wrenches.
Caution
When the pipings are
disconnected, protect the
both openings from entering
moisture.
21