SiBE04-624
2.5

Automatic Operation

Operation
∗ Refer to the operation manual for details.
Features
When the AUTO mode is selected with the remote controller, the microcomputer automatically
determines the operation mode from cooling and heating according to the room temperature
and setting temperature at the time of the operation startup, and automatically operates in that
mode.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature at the main unit setting temperature.
Details
1. Remote controller setting temperature is set as automatic cooling / heating setting
2. Main unit setting temperature equals remote controller setting temperature plus correction
3. Operation ON / OFF point and mode switching point are as follows.
4. During initial operation
Function and Control
temperature (18 to 30°C).
value (correction value: 0 deg).
Heating → Cooling switching point:
Room temperature ≥ Main unit setting temperature +2.5 deg.
Cooling → Heating switching point:
Room temperature < Main unit setting temperature –2.5 deg.
Thermostat ON / OFF point is the same as the ON / OFF point of cooling or heating
operation.
Room temperature ≥ Remote controller setting temperature: Cooling operation
Room temperature < Remote controller setting temperature: Heating operation
Heating /
cooling switching point
(Heating thermostat
OFF point)
Main unit setting
temperature
(Cooling thermostat
OFF point)
Cooling /
heating switching point
Cooling
operation
AUTO operation
Heating
operation
With no compressor capacity supplied
With compressor capacity supplied
Main Functions
(R5985)
2.5 deg.
or higher
(1.5 deg.)
or higher
Less than
(2.0 deg.)
2.5 deg.
or higher
Cooling
operation
(R3302)
31