SiBE04-624
3.7
Input Current Control
Detail
Stop zone
Step down zone
Steady zone
Return zone
Function and Control
I1
I2
I3
Class
I1 (A)
I2 (A)
I3
After 5 seconds in this zone the compressor is stopped
I 2
The maximum limit of the compressor frequency in this control is defined as operation
frequency - 2 Hz.
After this, the output frequency is pulled down by 2 Hz every second until it reaches the
steady zone.
Keeping the present maximum frequency.
Limit of the frequency is cancelled.
Compressor Stop
Cooling
28
42
50
14
14
14
5.5
7.5
10.0
4.5
6.5
9.0
*I2 has the cooling and heating current,
respectively.
Ambient temperature
Control Specification
Stop Zone
Step down Zone
Steady Zone
Return Zone
(R5907)
Heating
28
42
50
14
14
14
10.5
10.5
10.5
9.5
9.5
9.5
(R5917)