Advertisement

UPS Installation Plan and Unpacking
The power wiring terminals are pressure terminations, UL and CSA rated at 90°C. See Table 3-5 for external
power cable terminations.
Figure 4-7 and Figure 4-8 show the location of the UPS power cable terminals.
Table 3-5. UPS External Power Cable Terminations for the Eaton 9E-40, 9E–60/40, and 9E–60/60
Terminal Function
AC Input to UPS Rectifier
AC Input to Bypass
AC Output to Critical Load
DC Input from External Battery
Customer Ground
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-6.
3-8
Eaton 9E UPS (40–60 kVA, 208/220V) Installation and Operation Manual P-164000058—Rev 4
Terminal
Function
L1
Phase A
L2
Phase B
L3
Phase C
N
Neutral
L1
Phase A
L2
Phase B
L3
Phase C
N
Neutral
L1
Phase A
L2
Phase B
L3
Phase C
N
Neutral
+
Battery (+)
Battery (-)
Ground
Ground
Number and Size of Pressure
Termination
AWG or kcmil
1 – #6-250
1 – #6-250
1 – #6-250
2 – #6-250
1 – #6-250
1 – #6-250
1 – #6-250
2 – #6-250
1 – #6-250
1 – #6-250
1 – #6-250
2 – #6-250
2 – #6-250
2 – #6-250
4 – #6-300
www.eaton.com/powerquality
Tightening Torque
Nm (lb in)
Screw Size and Type
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
22.6 (200)
1/4 in. Hex
31.1 (275)
5/16 in. Hex