4-2 Function Mode
Frequency Conversion Coefficient
This function displays a conversion value obtained by multiplying the Inverter output frequency by
the coefficient set in [b086]. This helps display the actual physical value on the monitor.
Function code
b086
Related functions
Displayed value [d007] = "Output frequency [d001]" × "Frequency conversion coefficient [b086]"
4
(Display) [d007]
0.00 to 99.99
100.0 to 999.9
1000. to 9999.
1000 to 3996
(Setting range) [b086]
0.1 to 99.9: 0.
(Example) When the output frequency [d001] = 50.0 Hz, and
the frequency conversion coefficient [b086] = 1.1,
the monitor [d007] displays "55.0" through 50.0 × 1.1 = 55.0.

STOP Key Selection

•You can select whether to enable the STOP key on the Digital Operator, even if the RUN command
is set to the control terminal block (terminal).
•The trip reset function via the STOP/RESET key works according to this setting.
Parameter No.
b087
Free-run Stop Selection and Stop Selection
Activating the free-run stop (FRS) function shuts off the Inverter output, letting the motor go into
free-run status.
Parameter No.
b088
b091
b003
Related functions
•Helps stop the motor using a mechanical brake such as an electromagnetic one.
4-35
Item
Frequency conversion
0.1 to 99.9
coefficient
: Displays in increments of 0.01.
: Displays in increments of 0.1.
: Displays in increments of 1.
: Displays in increments of 10.
: Can be set in increments of 1.
Function name
00: Enabled
STOP key selection
01: Disabled
Function name
00: 0 Hz start
Free-run stop selection
01: Frequency pull-in restart
00: Deceleration → Stop
Stop selection
01: Free-run stop
Retry wait time
0.3 to 100.0
Data
Default setting
d007
Data
Default setting
Data
Default setting
C001 to C006
Unit
1.0
Unit
00
Unit
00
00
1.0
s