4-2 Function Mode
Output Over Set Frequency (02: FA2)
•Outputs a signal when the output frequency has exceeded the arrival frequencies during
acceleration/deceleration set in [C042, C043 (FA2)].
4
Overload Warning
If the load is too large, this function outputs an overload warning signal, allowing you to readjust the
overload level to prevent a trip.
This helps prevent mechanical damage due to an overload in the conveyors, or an operation line
stop due to an overload trip of the Inverter.
Data
03
Available input terminals
Required settings
Parameter No.
C041
4-55
C042
f on
Output frequency
FA2
Symbol
Function name
OL
Overload warning
Function name
0.0: Does not operate.
Overload warning
0.1 to Rated current × 200%:
level
Overload limit level
b022
Overload warning level
C041
Output current
OL
C043
f off
Status
The Inverter output current has exceeded the C041 set
ON
value.
The Inverter output current has not reached the C041
OFF
set value.
P1-PC, P2-PC, MA-MC (or MB-MC)
C021, C026, C041
Data
Outputs OL signal when reaching the
overload warning level.
f on :1% of max. frequency
f off :2% of max. frequency
Description
Default setting
Rated current
Unit
A