Setting
ModBus communication requires the following settings. Be sure to set the parameters as shown
below.
If the parameter settings are changed, the new settings are enabled at the point of change.
However, ModBus communication will not start until "485" is selected with the 485/OPE selector
and the Inverter is turned on again.
The parameters of C070s cannot be changed or set through ModBus communication. Set using the
attached Digital Operator.
Parameter No.
Function name
A001
Frequency reference selection
A002
RUN command selection
C071
Communication speed selection
C072
Communication station No. selection 1 to 32
C074
Communication parity selection
C075
Communication stop bit selection
C078
Communication wait time
Communication Procedure
•Follow the procedures below in regard to communication between the external control device and
the Inverter.
External controller
Inverter
1: Frame to be sent from the external control device to the Inverter (Query)
2: Frame to be returned from the Inverter to the external control device (Response)
The Inverter returns a response (Frame (2)) only after receiving a query (Frame (1)) and does not
output a response positively.
Below is each frame format (command).
Message Configuration: Query
Header (Silent interval)
Slave address
Function code
Trailer (Silent interval)
00 (VR), 01 (Terminal), 02 (Digital Operator), 03 (Modbus
communication)
01 (Terminal), 02 (Digital Operator), 03 (Modbus
communication)
04 (4800 bps), 05 (9600 bps), 06 (19200 bps)
00 (No parity), 01 (Even parity), 02 (Odd parity)
1 (1 bit), 2 (2 bits)
0 to 1000 ms
1
Wait time (silent interval +C078)
Data
Error check
4-2 Function Mode
Description
Time
2
4
4-66