Omron SYSDRIVE MX SERIES User Manual page 134

Multi-function compact inverter
Table of Contents

Advertisement

4-2 Function Mode
•You can also select a multi-step speed by turning on/off the multi-step speed terminals (CF1 to
CF4) and set the multi-step speed frequency with F001.
Multi-step speed terminals
Multi-step
speed
CF4
0th
1st
2nd
3rd
OFF
4th
5th
4
6th
7th
8th
9th
10th
11th
ON
12th
13th
14th
15th
Jogging Operation Function
•The motor rotates while the input is turned ON.
Data
06
Available input terminals
Required settings
Parameter No.
A038
A039
•Allocate 06 (JG) to the desired multi-function input.
4-43
CF3
CF2
CF1
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
Symbol
Function name
JG
Jogging operation
Function name
Jogging frequency
Jogging stop selection
4th
5th
3rd
6th
2nd
7th
1st
8th
CF1
CF2
CF3
CF4
FW
Status
ON
OFF
C001, C002, C003, C004, C005, C006
A002 = 01, A038 > b082, A038 > 0, A039
Data
0.00/Starting frequency to 9.99
00: Free-run stop
01: Deceleration stop
02: DC injection braking stop
11th
10th
Frequency reference
12th
from the Digital Operator
9th
13th
or the external analog
14th
input terminal
15th
0th
Description
Operates at the set jogging frequency.
Stop
Default setting
6.00
00
Unit
Hz
Hz