Omron SYSDRIVE MX SERIES User Manual page 152

Multi-function compact inverter
Table of Contents

Advertisement

4-2 Function Mode
Specifications of Multi-function Output Terminals P1, P2
•Below are the specifications of multi-function output terminals P1, P2.
Inverter's
internal circuitry
C031 to C032 set values
4
•Connect multi-function output terminals P1 and P2 at the same sink/source logics.
•The PC terminal acts as a common terminal at sink/source logics.
Relay Output Contact Selection
•The relay output terminal has an SPDT contact configuration. Below is the operation.
Inverter's internal
circuitry
(a) When used as an alarm terminal
C036
Power
set
supply
value
ON
00
OFF
ON
01
OFF
4-61
Power
supply
ON
00
(NO contact)
OFF
ON
01
(NC contact)
OFF
MB MA MC
Output terminal status
Inverter
status
MA-MC
MB-MC
Abnormal
Closed
Open
Normal
Open
Closed
Open
Closed
Abnormal
Open
Closed
Normal
Closed
Open
Open
Closed
P2
PC
P1
Output status
ON
OFF
ON
OFF
Electrical specifications
Output terminal
Max. contact
capacity
MA-MC
Min. contact
capacity
Max. contact
capacity
MB-MC
Min. contact
capacity
(b) When used as an output terminal
C036
Power
set
supply
value
ON
00
OFF
ON
01
OFF
Electrical specifications
Between each terminal and PC
Voltage drop 4 V max. at power-on
Max. allowable voltage: 27 V DC
Max. allowable current: 50 mA
Resistance load
Inductive load
250 V AC, 2 A
250 V AC, 0.2 A
30 V DC, 3 A
30 V DC, 0.6 A
100 V AC, 10 mA
5 V DC, 100 mA
250 V AC, 1 A
250 V AC, 0.2 A
30 V DC, 1 A
30 V DC, 0.2 A
100 V AC, 10 mA
5 V DC, 100 mA
Output terminal status
Output
signal
MA-MC
ON
Closed
OFF
Open
Open
ON
Open
OFF
Closed
Open
MB-MC
Open
Closed
Closed
Closed
Open
Closed

Hide quick links: