5-2 Troubleshooting

5-2 Troubleshooting
Situation
The motor
No voltage
doesn't
observed for
work.
Inverter outputs
U/T1, V/T2, and
W/T3.
5
Voltage
observed for
Inverter outputs
U/T1, V/T2, and
W/T3.
Motor
rotation is
in reverse.
5-5
Possible cause
• Is the A001 setting (frequency
reference selection) correct?
• Is the A002 setting (RUN command
selection) correct?
• Is the [485/OPE] communications
selector status correct?
• Is the [TM/PRG] selector status
correct?
• Is power supplied to terminals R/L1,
S/L2, and T/L3? If so, the POWER
LED indicator should light up.
• Does the display show "E **"?
• Is the allocation of the multi-function
input correct?
• Is the RUN key (RUN command)
turned on?
• Are FW (or RV) input and terminal SC
or PSC connected?
• Is the [SK/SR] selector status correct?
• Is the frequency set with F001
selected?
• Is the potentiometer connected to
terminals FS/FV/FC?
• Are RS and FRS inputs still turned
on?
• Is the motor restrained?
• Or is it overloaded?
• Are output terminals U/T1, V/T2, and
W/T3 correct?
• Is the phase sequence of the motor U/
T1, V/T2, W/T3, and is the rotation in
forward or reverse?
• Is the control circuit terminal correct?
• Is F004 set correctly in the motor
rotation direction selection via the
Digital Operator?
Remedy
• Check the A001 setting.
• Check the A002 setting.
• Check the [485/OPE]
communications selector.
• Check the [TM/PRG] selector.
• Check the connections of terminals
R/L1, S/L2, T/L3 and U/T1, V/T2,
W/T3.
• Turn on the power.
• Press the Mode key to check the
situation, and then reset.
• Check the terminal allocation:
C001 to C006
• Turn on the RUN key (RUN
command).
• Connect FW (or RV) input to terminal
SC or PSC.
• Check the [SK/SR] selector.
• Press the key to set.
• If terminal mode is selected, set the
potentiometer to FS/FV/FC.
• Turn off these inputs.
• Release the restraint and reduce the
load.
• Operate the motor separately.
• Connect according to the motor
phase sequence. (Generally, U/T1,
V/T2, W/T3 in forward)
• Select FW for forward and RV for
reverse.