Omron SYSDRIVE MX SERIES User Manual page 165

Multi-function compact inverter
Table of Contents

Advertisement

*1. There is no response for broadcasting.
*2. Since the change data comprises both MSB and LSB as a set, make the byte to be an even number by adding
1, even if the byte that actually needs to be changed is an odd number.
Refer to "<Exception Response>" below if writing into multiple coils cannot be performed normally.
<Writing Into Multiple Holding Registers [10h]>
Writes into consecutive multiple holding registers.
(Example)
Set 1st acceleration time 1 (F002) to "3000 sec." for the Inverter with slave address 1.
The data resolution of the holding registers "0024h, 0025h" of acceleration time 1 (F002) is 0.01
seconds. To set 3000 seconds, set change data to "300000 (493E0h)".
Query
No.
Field name
*1
1
Slave address
2
Function code
3
Start address (MSB)
4
Start address (LSB)
Number of holding
5
registers (MSB)
Number of holding
6
registers (LSB)
*2
7
Number of bytes
8
Change data 1 (MSB)
9
Change data 1 (LSB)
10
Change data 2 (MSB)
11
Change data 2 (LSB)
12
CRC-16 (MSB)
13
CRC-16 (LSB)
*1. There is no response for broadcasting.
*2. Specify the number of bytes to be changed, not the number of holding registers.
Refer to "<Exception Response>" below if writing into the multiple holding register cannot be per-
formed normally.
<Exception Response>
The master requires a response for a query except for broadcasting. Though the Inverter should
return a response corresponding with the query, it returns an exception response if the query has
an error.
Response
Example
(HEX)
01
10
00
24
00
02
02
00
04
93
E0
54
FD
4-2 Function Mode
No.
Field name
1
Slave address
2
Function code
3
Start address (MSB)
4
Start address (LSB)
Number of holding
5
registers (MSB)
Number of holding
6
registers (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
4
Example
(HEX)
01
10
00
24
00
02
01
C3
4-74