Inspection
Inspection
part
item
Main
General
Insulation resistance test
circuit
(between main circuit terminal
and ground terminal)
Check that the screws
are secure.
Check that no part has
indications of overheating.
Terminal
Check that there is no
block
damage.
Smoothing
Check that there is no
capacitor
liquid leakage.
Check that the safety
valve has not come out.
Check that there are
no bulges.
Relay
Check that there is no
terminal
abnormal sound
block
during operation.
Resistor
Check that there are
no large fissures or
discoloration in the
resistance insulation.
Cooling fan
Check that there are
no abnormal vibrations
or sounds.
Check that there is no
dirt or dust.
Check that the fan is
mounted correctly.
*1. The life of the capacitor depends on ambient temperatures. Refer to "Product Life Curve" (App-17).
*2. Clean the Inverter periodically. Accumulated dust in or on the cooling fan or heat sink can cause the Inverter
to overheat.
Inspection
period
Inspection point
Daily
Periodic
*2
6-1 Inspection and Maintenance
Inspection
Criteria
method
Megger
5 MΩ min.
check
(Refer to 6-2.)
Tighten
Tightening torque
securely
(excluding
terminal block)
•M 3.5: 0.8 N•m
•M 4 : 1.2 N•m
Visual
inspection
Visual
No faults
inspection
Visual
No faults
inspection
Acoustic
No faults
inspection
Visual
No faults
inspection
Rotate
Smooth rotation
manually when
the power is off.
Visual
inspection
Visual
inspection
Standard
replacement
Meter
period
500 V DC
megger
*1
Tester
2 to 3 years
6-4
6