5-7-3

STOP Key Selection

• Enable/disable the STOP/RESET key on the Digital Operator.
• This setting is enabled when the 1st/2nd RUN Command Selection (A002/A202) is not set to 02 (Dig-
ital Operator).
However, when the 1st/2nd RUN Command Selection (A002/A202) is set to 02 (Digital Operator), the
STOP/RESET key is enabled independent of this setting.
Parameter
No.
b087

STOP Key Selection

Data
00
01
02
Precautions for Safe Use
The STOP/RESET key on the Digital Operator is enabled only when the STOP Key Selection
(b087) is set to 00: Enabled (default data).
Be sure to provide a separate emergency stop switch.
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Function name
STOP command via STOP/RESET key on
Digital Operator
Enabled
Disabled
Disabled
Data
00:
Enabled
01:
Disabled
02:
Only RESET enabled
Trip reset via STOP/RESET key on
5 Basic Settings
Default
Unit
data
00
Digital Operator
Enabled
Disabled
Enabled
5 - 41