External I/O Signal Logic Switching Function - Mitsubishi Melsec-Q QD75P1 User Manual

Programmable logic controller q-series
Hide thumbs Also See for Melsec-Q QD75P1:

Advertisement

13 COMMON FUNCTIONS

13.4 External I/O signal logic switching function

Setting item
Input signal logic
Pr.22
selection
Output signal logic
Pr.23
selection
Refer to Section 5.2 "List of parameters" for the information on detail settings.
This function switches the signal logic according to the external equipment connected
to the QD75.
For the system in which drive unit READY with b-contact, upper limit switch, and lower
limit switch are not used, the parameter logic setting can be controlled without wiring if
it is changed to a "positive logic".
When the drive unit READY, upper limit switch, and lower limit switch are used, ensure
to use them with b-contact.
The details shown below explain about the "External I/O signal logic switching
function".
[1] Parameter setting details
[2] Precautions on parameter setting
[1] Parameter setting details
To use the "External I/O signal logic switching function", set the parameters
shown in the following table.
• Selection of logic of signals input from external source to
QD75
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9 to b15
• Selection of logic of signals output from QD75 to external
source
b0
b1 to b3
b4
b5 to b15
[2] Precautions on parameter setting
(1) The external I/O signal logic switching parameters are validated when the
PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right after
power-on.)
(2) If each signal logic is set erroneously, the operation may not be carried out
correctly.
Before setting, check the specifications of the equipment to be used.
Setting details
Lower limit
Upper limit
Drive unit
READY
0: Negative logic,
Stop signal
1: Positive logic
External
command signal
Zero signal
Near-point signal
Unused
Set "0".
Manual pulse
0: Negative logic,
generator input
1: Positive logic
Unused
Set "0".
Command pulse
0: Negative logic,
signal
1: Positive logic
Unused
Set "0".
Deviation counter
0: Negative logic,
clear signal
1: Positive logic
Unused
Set "0".
13 - 7
MELSEC-Q
Buffer memory address
Factory-set
initial value Axis 1 Axis 2 Axis 3 Axis 4
0
31
181
331
0
32
182
332
481
482