15 TROUBLESHOOTING
Classification
Error
of errors
code
Outside linear
504
movement amount
range
Positioning
operation
Large arc error
506
deviation
Error name
• When the parameter "interpolation
speed designation method"
performs a linear interpolation in
setting a "composite speed", the
axis movement amount for each
positioning data exceeds
1073741824(2
• The positioning address is
–360.00000 or less or 360.00000
or more using INC instruction,
where the control unit is set to
"degree" and software stroke limit
upper limit is not equal to the
software stroke limit lower limit.
When an arc is interpolated by the
designation of the center point, a
difference between a radius of start
point-center point and a radius of
end point-center point exceeds the
parameter "Circular interpolation
error allowable limit".
Error
At start: The system will not operate.
30
).
During operation:
At start: The circular interpolation
During operation :
15 - 12
MELSEC-Q
Operation status at error occurrence
The system stops
immediately.
control by center point
designation is not executed.
The system will stop
immediately.