High-Speed Counter Module User’s Manual (Hardware) QD62-H01 QD62-H02 Thank you for buying the Mitsubishi general-purpose programmable controller MELSEC-Q Series Prior to use, please read both this manual and detailed manual thoroughly and familiarize yourself with the product. MODEL QD62-H01/H02-U MODEL...
Page 2
SAFETY PRECAUTIONS (Always read before starting use) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. For the safety instructions of the programmable controller system, please read the CPU module user's manual.
Page 3
[INSTALLATION PRECAUTIONS] CAUTION Use the programmable controller in an environment that meets the general specifications contained in the CPU user's manual to use. Using this programmable controller in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product.
Page 4
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
Page 6
SH-080036 User's Manual (13JL95) This manual describes only specifications of the QD62-H01/H02 that differ from the specifications of the QD62. The manual mentioned above covers the usage of the QD62-H01/H02. When referring, replace the model name “QD62” with “QD62-H01/H02”. For the details of differences between the QD62-H01/H02 and QD62, refer to Section 6.
This user’s manual describes the specifications and the part names of the following modules that are used with the CPU module for MESLEC-Q series: Model QD62-H01 High-speed Counter Module (hereinafter referred to as QD62-H01), Model QD62-H02 High-speed Counter Module (hereinafter...
2. Performance Specifications The following table shows the performance specifications of the high-speed counter modules: Model QD62-H01 QD62-H02 Item Number of occupied I/O 16 points (I/O assignment: Intelligent 16 points) point 2 channels Number of channels 1-phase input, 2-phase input...
Page 9
= 5 μs or less 50kPPS 10kPPS 7kPPS t = 50 μs 5kPPS — t = 500 μs — 500PPS 250PPS Remarks For general specifications of the QD62-H01 and QD62-H02, refer to the user’s manual for the CPU module used.
3. Installation 3.1 Handling Precautions This section describes the precautions on handling the module. 1) Do not drop or give a strong impact to the module case and/or connecter. 2) Do not remove the printed-circuit board of the module from the case. Doing so may cause a failure.
Serial number plate coincidence signal output section is broken. *: The external appearance of the QD62-H02 is the same as that of the QD62-H01, except for the model name. Terminal number QD62-H01/H02 Signal name Phase A pulse input 24V Phase A pulse input 12V...
2) For 1-phase input, always perform pulse input wiring on the Phase A side. 3) When pulse status noise is input, the QD62-H01/H02 may miscount. 4) Provide the following measures against noise for high-speed pulse input: a) Always use a shielded twisted pair cable and provide grounding.
External power supply The terminal number in parentheses is for Channel 2. POINT When wiring the QD62-H01/H02 and the encoder, separate the power supply cable and signal cable line. The following diagram figure shows an example. [Wiring example] QD62-H01/H02 24 V...
Page 14
Wiring example with a voltage output type encoder (5VDC) QD62-H01/H02 Encoder 24 V A20(A13) Phase A 12 V B20(B13) Shielded twisted pair cable A19(A12) Shield ABCOM B19(B12) 24 V A18(A11) 12 V Phase B B18(B11) Shielded twisted pair cable...
Page 15
When the coincidence output (EQU terminal) is used, an external power supply of 10.2 to 30VDC will be required for operation of the internal photocoupler. A wiring example is shown below. a) For QD62-H01/H02 (Sink output type) QD62-H01/H02 EQU1 A06(A05)
The same specifications apply for the QD62-H01/H02 and QD62, excluding those described above. When the manual for the QD62 is referred for the QD62-H01/02, use the specifications in this manual as for the items described above. 2) GX Configrator CT In GX Configrator CT, the “QD62-H01”...
3) GX Developer GX Developer does not support the display of the model names for the QD62-H01/H02. GX Developer displays the “QD62” as the model name for the QD62-H01/H02. 7. External Dimensions QD62-H01 QD62-H01 23 (0.91) 46 (1.81) 90 (3.54) 27.4 (1.08)
Page 18
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi;...