9 MAJOR POSITIONING CONTROL
Setting item
Cd.3
Positioning start No.
Cd.9
Current value changing
Refer to Section 5.7 "List of control data" for details on the setting details.
Positioning start signal
PLC READY signal
QD75 READY signal
Start complete signal
BUSY signal
Positioning complete signal
Error detection signal
Fig. 9.21 Changing to a new current value using the start No. (No. 9003) for a current value changing
Setting method for the current value changing function
The following shows an example of a sequence program and data setting to
change the current value to a new value with the positioning start signal. (The
Md.20
"
Current feed value is changed to "5000.0 m" in the example shown.)
(1) Set the following data.
(Set with the sequence program shown in (3), while referring to the start time
chart shown in (2).)
Setting
value
9003
50000
(2) The following shows a start time chart.
V
[Y10]
[Y0]
[X0]
[X10]
[XC]
[X14]
[X8]
Md.20 Current feed value
Cd.3 Positioning start No.
Cd.9 Current value changing
Setting details
Set the start No. "9003" for the new current value.
Md.20
Set the new "
Current feed value".
Address during positioning execution
Data No. during positioning execution
9 - 108
MELSEC-Q
Buffer memory address
Axis 1 Axis 2 Axis 3 Axis 4
1500
1600
1700
1800
1506
1606
1706
1806
1507
1607
1707
1807
Start of data No. 9003
t
50000
9003
50000