Download Print this page

Mitsubishi Melsec-Q QD75P1 User Manual page 608

Programmable logic controller q-series
Hide thumbs Also See for Melsec-Q QD75P1:

Advertisement

15 TROUBLESHOOTING
Warning storage
(1) When an axis warning occurs, the warning code corresponding to the warning
details is stored in the following buffer memory (
axis warning No. storage.
Axis No.
1
2
3
4
(2) When an axis warning occurs in a positioning operation, etc., "1" is set in bit 9
(b9) of the following buffer memory (
Axis No.
1
2
3
4
[3] Resetting errors and warnings
An error or warning state is canceled after the following processing has been
carried out by setting a "1" in the address [1502 (for axis 1)], [1602 (for axis 2)],
[1702 (for axis 3)], and [1802 (for axis 4)] of the buffer memory for axis error
Cd.5
resetting (
Axis error detection signal turned OFF
Md.23
"
Axis error No." cleared
"
Md.24
Axis warning No." cleared
Changing of "
"
Md.31
Axis warning detection (b9)" turned OFF
[4] Invalid operations
For the following operations, the setting details will be invalidated, and an error or
warning will not occur.
Speed change during machine OPR
Speed change before operation
(Speed override change, skip command, continuous operation interruption
request, target position change request)
Axis stop during axis stop
Axis sudden stop during axis stop
Axis stop before axis operation
Axis sudden stop before axis operation
[5] Confirming the error and warning definitions
The error and warning definitions can be confirmed with the error and warning
codes. Confirming them requires GX Developer or GX Configurator-QP. For
details, refer to GX Developer Operating Manual or GX Configurator-QP
Operating Manual. (Refer to Section 15.2 and Section 15.3 for details of the error
and warning codes.)
Buffer memory address
807
907
1007
1107
Md.31
Buffer memory address
817
917
1017
1117
Axis error reset).
Md.26
operation status" from "Error" to "Standby".
15 - 4
MELSEC-Q
Md.24
Axis warning No.) for
Status) for axis status storage.