5 Replacing DC SAN Director
field-replaceable units (FRUs)
This chapter provides information for replacing the following components:
IMPORTANT:
The FRUs in the DC SAN Director can be removed and replaced without special tools. The DC SAN
Director can continue operating during many of the FRU replacements if the conditions specified in
the procedure are followed.
• "Replacing the chassis
• "Replacing the cable management
• "Replacing a Director
• "Replacing a Director blade filler
• "Replacing a control processor blade
• "Replacing a core switch blade
• "Replacing a power
• "Replacing a blower
• "Replacing the WWN bezel (logo plate) and WWN
• "Replacing SFPs and
• "Replacing the DC SAN Director
Replacing the chassis door
The chassis door must be installed to ensure the DC SAN Director meets EMI and other regulatory
certifications. The replacement procedure for the chassis door takes less than 5 minutes.
Removing the chassis door
To remove the chassis door (see
NOTE:
The door is not hinged. It installs straight on the chassis by snapping four ball studs located on the
chassis into receiving hardware on the door in the cabinet.
1.
Grip the side of the door.
2.
Gently pull the door straight out from the chassis until it snaps out of the ball studs on the chassis.
door" on page 73
comb" on page 74
blade" on page 75
panel" on page 78
(CP8)" on page 79
(CR8)" on page 86
supply" on page 88
assembly" on page 89
XFPs" on page 96
chassis" on page 97
Figure 26
on page 74):
HP StorageWorks DC and DC04 SAN Backbone Director Switches
card" on page 91
73