Installing The Dc04 San Director Shipping Brackets; Cabinet Rail-To-Rail Depths - HP A7533A - Brocade 4Gb SAN Switch Base Hardware Reference Manual

Hp storageworks dc and dc04 san backbone director switches hardware reference guide (5697-7814, february 2009)
Hide thumbs Also See for A7533A - Brocade 4Gb SAN Switch Base:
Table of Contents

Advertisement

7.
Install the cable management finger assembly. See
Installing a cable management finger

Installing the DC04 SAN Director shipping brackets

This section describes how to install the DC04 SAN Director shipping brackets. (See
brackets are required when the DC04 SAN Director is shipped installed in a cabinet.
1.
Before installing the DC04 SAN Director in the cabinet, remove the 10 flathead 6-32 screws
located on both the left and right side chassis panels. See
2.
Install both side plates using the ten 6-32 panhead screws supplied with the kit.
NOTE:
The left and right side plates are different. The left side and right side plates are marked with
"A" and "B" respectively. See
NOTE:
The side plates have five sets of discrete holes, marked 27 through 31. Use the holes that
correspond with the cabinet's rail-to-rail depth. See
in/lbs.
3.
Install the DC04 SAN Director in the cabinet.
4.
Install the clip nuts or nut retainers.
The clip nuts are used with cabinets that have square holes, and nut retainers are used with
cabinets that have round holes. The locations of the clip nuts or nut retainers match the location
for the port-side rack brackets.
5.
Secure the L-brackets to the cabinet rails using the six 10-32 panhead screws with square cone
washers supplied with the kit. Tighten the screws to 32 in/lbs.
NOTE:
The left and right side brackets are different. The left side and right side L-brackets are marked
with A and B respectively. See
6.
After mounting the L-brackets to the rails, secure them to the side plates using the 18 10-32
panhead screws with square cone washers supplied with the kit. See
screws to 32 in/lbs.
Table 29 Cabinet rail-to-rail depths
Column ID
Rail-to-rail depth (inches)
136
DC04 SAN Director Installation
assembly, page 171.
Figure
46.
Figure
47.
27
28
27–27.5
27.5–28.5
Figure
46.
Table
29. Tighten the screws to 10
Figure
29
30
28.5–29.5
29.5–30.5
Figure
45). These
47. Tighten the
31
30.5–31