Replacing A Control Processor Blade (Cp8); Dc04 San Director Blade Filler Panel - HP A7533A - Brocade 4Gb SAN Switch Base Hardware Reference Manual

Hp storageworks dc and dc04 san backbone director switches hardware reference guide (5697-7814, february 2009)
Hide thumbs Also See for A7533A - Brocade 4Gb SAN Switch Base:
Table of Contents

Advertisement

2.
Slide the filler panel into the slot until it is firmly seated.
3.
Tighten the thumb screw at the bottom of the panel.
4.
Replace the chassis door (see
Figure 66 DC04 SAN Director blade filler panel

Replacing a control processor blade (CP8)

This section describes how to remove and replace a control processor (CP8) blade. Each DC04 SAN
Director has two CP8 blades, which are located in slot 4 and slot 5.
NOTE:
If the new CP blade does not have the same firmware as the active CP blade, you must upgrade the
new blade to the active CP blade's firmware version.
The replacement procedure for the CP blade takes approximately 30 minutes. The following items
are required for the CP blade replacement:
ESD grounding strap
Workstation computer
Serial cable
IP address of an FTP server for backing up the DC04 SAN Director configuration
Phillips #2 screwdriver
"Installing the chassis
HP StorageWorks DC and DC04 SAN Backbone Director Switches
door" on page 170).