Troubleshooting Errors When Turning On Power - Omron NS10-TV Series Programming Manual

Ns-series programmable terminals
Hide thumbs Also See for NS10-TV Series:
Table of Contents

Advertisement

Section 5 Troubleshooting and Maintenance
NS Series Programming Manual
5-2-2

Troubleshooting Errors when Turning ON Power

This section describes possible errors immediately after power is turned ON to the PT and the coun-
termeasures for these errors.
No.
1
FATAL ERROR No. 01: Touch Panel is
not connected: Please contact your
OMRON service center.
2
FATAL ERROR No. 02: SRAM Initializa-
tion Error: Please contact your OMRON
service center.
3
FATAL ERROR No. 03: MAC Address
Error: Please contact your OMRON
service center.
4
FATAL ERROR No. 04:
PT Model type Identify error.
10
ERROR No. 10: File System Error:
Please recover the system program.
10
ERROR No. 10: Fail in loading files or
executing program: Please recover the
system program.
10
ERROR No. 10: Fail in loading files:
Please recover the system program.
11
ERROR No. 11: Fail in loading files:
Please reinstall the system program.
11
ERROR No. 11: Device check program
error: Please reinstall the system
program.
11
ERROR No. 11: SRAM check program
error: Please reinstall the system
program.
11
ERROR No. 11: IP Address Setting
Error: Please reinstall the system
program.
Message
Cause
Touch panel error.
Hardware error in log
SRAM.
Incorrect MAC address.
The PT model cannot be
determined.
File system is corrupted.
(A hardware fault
occurred or power was
interrupted during
writing.)
File reading or program
execution failed.
Read-only file is being
transferred to the PT.
File reading failed.
File reading failed.
Hardware check program
is corrupted.
Log SRAM check
program is corrupted.
IP address setting
program is corrupted.
5-9
5-2 Error Messages
Possible countermeasure
The PT may need repaired.
Contact your nearest OMRON
representative.
The PT may need repaired.
Contact your nearest OMRON
representative.
Reinstall the system program by
inserting the Memory Card con-
taining the recovery program in
the PT and resetting the PT or
turning the power supply OFF and
ON again. (Refer to 3-6 Using
Memory Cards in the Setup
Manual.) If a read-only file is
stored in the PT, perform a clean
install. After that, confirm that the
file is not read-only and transfer
the screen data to the PT. If the
same problem occurs after rein-
stalling the system program, the
PT may need repaired. Contact
your nearest OMRON representa-
tive.
Execute automatic download of
the system program. If the same
problem occurs after download-
ing, insert the Memory Card con-
taining the recovery program in
the PT and reset the PT or turn
the power supply OFF and ON
again. (Refer to 3-6 Using Mem-
ory Cards in the Setup Manual.)
If the same problem occurs after
reinstalling the system program,
the PT may need repaired.
Contact your nearest OMRON
representative.