Section 2 NS Series Functions
NS Series Programming Manual
Error Messages
Error
Cannot write in RUN mode.
Cannot clear error (When error
cleared from Error Information
Screen)
(Serial port receive error dis-
played)
Set address is out of range.
Please set other address.
Failed to read the Switch Box File
for NS file.
Cannot use the Switch Box
Function because no Host is
registered.
Cannot connect to this PLC
model.
Writing to this memory is not
possible.
Possible cause
An attempt has been made to
change the contents of words
while the PLC is in RUN mode.
The cause of the error has not
been cleared at the PLC.
Connection cable has been
disconnected or has come out of
the connection socket.
The Switch Box File for NS con-
tained incorrect address settings
is selected (e.g., set address
range is not correct).
The Switch Box File for NS not
found when returning to the
Switch Box Screen.
Settings in the Switch Box File for
NS are not correct.
An attempt was made to switch
from the user screen to Switch
Box Screen by operating
command button when no host
was set in Register Host.
The HOST type for PLC that is
not supported by Switch Box
function that was selected in the
host Selection Dialog Box.
Either Change Val or Bit Status
Button was pressed when
monitoring device that cannot be
written.
2-478
2-20 Special Functions
Remedy
Change the PLC to another
operating mode. The PLC
operating mode can be changed
from any device monitor screen.
Remove the cause of the error at
the PLC. Refer to the manual for
the connected PLC for details.
Check the connection between
the PT and the PLC. Refer to
Section 7 Maintenance and
Troubleshooting in the NS Series
Setup Manual .
Select the host with correct ad-
dress settings. Set addresses on
the Switch Box Utility again.
Transfer Switch Box File for NS
again. If error persists, make the
address settings on the Switch
Box Utility again.
Make the communications
settings on CX-Designer and
transfer the screen data
contained to the registered host
again.
Select a host that can be used on
the Switch Box Screen and
change the connected PLC type.
None
(Change the communications
address to write.)