Specifications - Omron E5 J Series Manual

Fuzzy self-tuning temperature controller with advanced pid (2 pid) contr
Table of Contents

Advertisement

E5 J

Specifications

Ratings
Supply voltage
Operating voltage range
Power consumption
Input
Current Transformer input
Control
Co
o
E5AJ/E5BJ/E5EJ
output
t
t
E5CJ
5CJ
Relay output
Voltage output
Current output
Control mode
Alarm output
Setting method
Indication method
Event input
Other functions
Note: It is possible to add other functions from the engineering level. Refer to the E5 J Operation Manual , obtainable from your OMRON
representative, for details.
100 to 240 VAC, 50 or 60 Hz
85% to 110% of rated supply voltage
E5AJ/E5EJ:
10 VA (at 100 VAC) to 14 VA (at 240 VAC)
E5BJ/E5CJ:
10 VA (at 100 VAC) to 12 VA (at 240 VAC)
Thermocouple (K/J/T/L/U/N) or platinum resistance thermometer (JPt100/Pt100), selectable
Connect an exclusive Current Transformer unit (E54-CT1 or E54-CT3)
Replaceable Output Unit (sold separately)
SPST-NO, 3 A at 250 VAC (resistive load)
20 mA at 12 VDC (with short-circuit protection)
4 to 20 mA DC with a load of 600 Ω max. and a resolution of approx. 2600
ON/OFF or PID control (2-PID) with fuzzy self-tuning and auto-tuning
E5AJ/E5EJ: Relay output, 2 independent SPST-NO contacts; 3 A, 250 VAC
E5BJ/E5CJ: Common 2 outputs, 2 independent SPST-NO contacts;
E5CJ: 1 A, 250 VAC; E5BJ: 3 A, 250 VAC
Digital setting via Up and Down Keys
Digital indications
Character heights: E5AJ: PV: 15 mm, SV: 10.5mm
E5EJ/E5BJ: PV: 14 mm, SV: 9.5 mm
E5CJ: PV: 12 mm, SV: 8 mm
Contact input:
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact input:
ON: residual voltage: 3 V max., OFF: leakage current: 1 mA max.
Key protection
Direct and reverse output selection
Multiple SP (four set points; up to four set points available on E5AJ/E5EJ by engineering level)
RUN/STOP (selected via external terminals) (E5AJ, E5EJ)
Heater burnout detection
24 V AC/DC, 50 or 60 Hz
10 VA (at 24 VAC)
6 W (at 24 VDC)
E5 J
3

Advertisement

Table of Contents
loading

Table of Contents