7. Running modes
7.1 Remote start/stop mode
To use the Remote start/stop mode, configure one of the digital input as Remote start/stop (Latched type input) and set the
controllerto Auto mode.
To start or stop the genset while in Remote start/stop mode, activate/deactivate (continuous signal) the pre-configured Remote start/
stop input. The controller latches the genset contactor when the controller confirms that all the engine and genset parameters are
within the configured thresholds. When the pre-configured input is deactivated the controller opens the genset contactor.