CGC 200 Operator's manual 4189340770
UK

3. Using the controller

3.1 Genset control mode and status

3.1.1 Genset control mode

There are three possible genset control modes:
Manual: The genset is started and stopped by pressing the push-buttons on the front panel.
Auto: The genset can be started using a remote signal.
Stop: The genset is stopped. In this mode, alarms can be reset and the display can be tested.
The genset can be on standby in the Auto and Stop modes.

3.1.2 Genset status

There are four possible genset statuses:
Stopped
Starting: this can include Crank, Fuel on and Not running
Running
Cooling down
See the Designer's handbook for more information about the controller functions and sequences. The De-
signer's handbook also has more information on the genset statuses listed above.

3.2 Basic tasks

3.2.1 Manual start

To start the genset manually:
1. Ensure that the controller is in Manual mode.
If the controller is in Auto mode, the LED next to
mode.
2. Press
.
The controller will run the start sequence. If everything is OK, the genset will start.

3.2.2 Auto start

For auto start:
1. Make sure that the controller is in Auto mode. The LED next to
If the controller is not in Auto mode, press
2. Send the remote start signal to the controller. The controller will run the auto start sequence. If everything
is OK, the genset will start.

3.2.3 Viewing operating values

To view operating values on the front panel, press
each time the button is pressed.
DEIF A/S
will be lit. Press
will be lit in Auto mode.
.
. The display will show a new set of operating values
Using the controller
to change to Manual
Page 12 of 43