Parameter
Shelt Temp Run Duration 0 to 720 min
Timers
Timers > Start/Stop
Parameter
Warm-Up Delay
Return To Mains Delay
Load Transfer Delay
Minimum voltage and frequency set points
Generator > Alternator Configuration
Parameter
Min Healthy Voltage
Min Healthy Frequency

4.2.5 Cyclic mode

In this mode, the genset operates for an adjustable amount of time during a mains failure. You can adjust the genset
operating hours and cooling down period. The maximum cycle is 12 hours.
To activate cyclic mode, go to Module > Cyclic Mode and tick the box next to Cyclic Mode.
User manual 4189341355A EN
Range
Range
0 to 60 s
0 to 600 s
1 to 60 s
Range
10 to 100 %
10 to 100 %
Default
60 min
Description
timer expires, the controller activates the
start sequence for the genset.
The genset operates for this time
duration when the shelter temperature is
too high.
Default
3 s
5 s
1 s
Default
40 %
40 %
Page 56 of 92