Huawei UPS5000-E User Manual page 163

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Overload
threshold (%)
Overcurrent
threshold (%)
Undercurrent
threshold (%)
Issue 06 (2023-08-25)
Description
Branch and mains current
overload alarm threshold.
When the branch current is
lower than the rated current
multiplied by the value of Br.
cur. shock protect (%) and
higher than the rated branch
current multiplied by the
value of Overload threshold
(%), the system generates a
branch overload alarm.
When the mains current is
higher than the rated mains
current multiplied by the
value of Overload threshold
(%), the system generates a
mains overload alarm.
Branch and mains
overcurrent threshold. When
the mains or branch current
is higher than the rated
mains or branch current
multiplied by the value of
Overcurrent threshold (%)
and lower than the rated
current multiplied by the
value of Overload threshold
(%), the system generates
an alarm.
Branch and mains
undercurrent threshold.
When the mains or branch
current is higher than the
rated mains or branch
current multiplied by the
value of Undercurrent
threshold (%) and lower
than the rated current
multiplied by the value of
Overcurrent threshold (%),
the system generates an
alarm.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 LCD Interface
Default Value
Value Range
100.0
100.0–120.0
80.0
80.0–100.0
60.0
30.0–80.0
155